Part 1: Primary cable, duct, and pull box standards

​Cable Type ​Voltage (Kilovolts) ​Minimum Bending Radius for Cable (millimetres) ​ ​Conduit Size (millimetres) ​Minimum Radius of Duct Bends ​In-Ground Pull Box Detailed Drawing Number
​Dressing Pulling​

1-1/C 1/0 AL XLPE CN-J

15 kV ​329 mm ​493 mm ​100 mm (4") ​915 mm (36") ​Drawing #1 - Part 1
​3-1/C 1/0 AL XLPE CN-J ​15 kV ​​329 mm ​493 mm ​​100 mm (4") ​915 mm (36") ​​Drawing #1 - Part 1
​3-1/C 500 MCM Cu
XLPE CN-J Triplexed
​15 kV ​​578 mm ​823 mm ​​150 mm (6") ​915 mm (36") ​​Drawing #1 - Part 2
​3-1/C 750 MCM Cu
XLPE CN-J Triplexed
​15 kV ​684 mm ​908 mm ​​​150 mm (6") ​1,219 mm (48") ​​​Drawing #1 - Part 2
​3-1/C 750 MCM Cu EPR LC Shield – J Triplexed ​15 kV ​631 mm ​899 mm ​​​150 mm (6") ​​1,219 mm (48") ​​​Drawing #1 - Part 2
​1-1/C #1/0 XLPE AL ​25 kV ​380 mm ​571 mm ​​​100 mm (4") ​915 mm (36") ​​Drawing #1 - Part 1
​3-1/C #1/0 XLPE AL ​​25 kV ​380 mm ​571 mm ​​​100 mm (4") ​915 mm (36") ​​Drawing #1 - Part 1
​3-1/C 500 MCM Al XLPE CN-J ​​25 kV ​523 mm ​785 mm ​​​​150 mm (6") ​915 mm (36") ​​​Drawing #1 - Part 2
​3 -1/C 750 MCM Cu
XLPE CN-J Triplexed
​​28 kV ​762 mm ​1,087 mm ​​​​150 mm (6") ​​1,219 mm (48") ​​​Drawing #1 - Part 2
  • EDTI reserves the right of final approval of the pull box size and location(s) prior to granting approval for construction.
  • Contact EDTI Customer Engineering Services for confirmation of the primary cable type, size, and voltage being installed for your specific site and to review the pulling calculation.
  • If pulling lengths exceed the maximum pulling tension of the cable, or the cumulative total of all bends between pulling points exceeds four 90-degree bends, pull box(es) must be installed (2012 Canadian Electrical Code Part 1 , 22nd Edition, Rule 12-940). .Contact EDTI for preapproval for shorter radius bend if proper depth of at service entry cannot be achieved.
  • See Drawing 29 for the primary voltage rating in your area.
  • Conduits must enter and exit the pull box at the same level.
  • Communication cables cannot share the same pull box with primary cables.
  • Please see examples A and B below, showing maximum pulling distances for two standard installations.

Part 2: Primary cable, duct, and pull box standards examples